Sizing & runtime
Battery Runtime Calculator
Estimate how long a battery will power a load, with optional Peukert correction for lead-acid batteries.
Formula
I = P ÷ (V × η) (or the current entered)
t(full) = H × (C ÷ (I × H))^k
t(usable) = t(full) × DoD
Worked example
100 Ah @ C20, 12 V, 60 W, k = 1, DoD 50% → I = 5 A → 20 h full → 10 h usable.
Limitations and warnings
- Peukert's law is an approximation that works best near constant current and room temperature.
- Real loads cycle on and off; use the average current.
Four values that are often confused
- Nominal capacity (Ah)
- Charge a battery delivers under rated conditions, usually over 20 hours (C20) at 25 °C.
- Usable capacity
- The part of the nominal capacity you can use without damaging the battery — about 50% for lead-acid, 80–90% for LiFePO4.
- Cranking current (CCA)
- Current deliverable for a short time in the cold to start an engine. It measures power, not stored charge, and cannot be converted to Ah.
- Stored energy (Wh)
- Ah × voltage. The right unit to compare batteries of different voltages.