Sizing & runtime

12 V, 24 V & 48 V Battery System Calculator

Size a battery bank for a 12, 24 or 48 V system and see how system voltage changes current.

h

d

%

Formula

I = P ÷ V(system)
Ah(bank) = P × h × days ÷ (V × DoD)
S = V(system) ÷ V(battery),  P = ⌈Ah(bank) ÷ Ah(battery)⌉

Worked example

500 W × 4 h, 1 day, 24 V, DoD 50%, 12 V 100 Ah batteries → 166.7 Ah bank → 2S2P = 4 batteries; current 20.8 A (41.7 A at 12 V).

Limitations and warnings

  • Higher system voltage lowers current, cable size and losses, but all equipment must be rated for it.

Four values that are often confused

Nominal capacity (Ah)
Charge a battery delivers under rated conditions, usually over 20 hours (C20) at 25 °C.
Usable capacity
The part of the nominal capacity you can use without damaging the battery — about 50% for lead-acid, 80–90% for LiFePO4.
Cranking current (CCA)
Current deliverable for a short time in the cold to start an engine. It measures power, not stored charge, and cannot be converted to Ah.
Stored energy (Wh)
Ah × voltage. The right unit to compare batteries of different voltages.